50KV Very Low Frequency high voltage generator | |
Precautions: 1.Before the use of this instrument in cable and generator pressure test, should be tested with megohmmeter, megger test no problem, can use the instrument. 2.Fully discharge the tested object with discharge rod before starting up, (the discharge rod using method is: first discharge with the current-limiting discharge end, then ground terminal). Ultra low frequency connection method with two booster:When using the booster I alone (test voltage is 30 KV or less), instrument control output I must be connected to booster I, don't connect control output II. When the booster I and booster II are used in series (test voltage is 80 KV or less), instrument control output I must be connected to booster I, and instrument control output II must be connected to booster II, absolutely not inversely connection! Otherwise the instrument or tested object will be damaged. WhatsApp:18164095486 | |